- Input may be through a coupler or gland.
- The outside surfaces shall be essentially of fireproof construction.
- If the input cable is protected by a ground-wire monitor that is terminated in the box, the enclosure shall include a ground-wire monitor test button.
- On single-output belt starters, the required circuit protection may be located in the load center.
- Each belt motor and/or belt auxiliary circuit shall have the following protection:
- Phase fault
- Overload
- Ground fault (may be provided at the power center)
- Any output circuit for equipment not associated for the belt operation shall be designed in accordance with the load center criteria.
- The following required belt motor safety circuits shall include a manual reactivation:
- Phase fault
- Overload
- Ground fault
- Belt slip circuits
- Pull cord circuits
- If the belt motor starter utilizes a programmable logic controller or other electronic controls, it shall comply with one of the following schemes to prevent starter operation due to failed outputs:
- Hard-wired safety circuits
- Status check feedback circuits
- Multi-motor starters utilizing plugs and receptacles shall have interlocks that trip all breakers when any plug is uncoupled. If the design of a motor (i.e. DC or synchronous AC) allows for generation of electrical power from a mechanical input, then precautionary measures must be taken to prevent electrical shock from regenerated power (minimum of warning labels).
- Any output circuits feeding power to stationary underground motors of one hundred brake horsepower or over shall be provided with a suitable meter to indicate the load on the machine.
-
Load Center
-
Surface Mine Fans
-
Track Mounted Carrier
-
Welding Cables
-
Stipulation of Settlement Between the PCA and DER DEP
-
Equipment Task Force
-
Miscellaneous Electrical Devices
-
Branch Circuits and Taps
-
Circuit Breaker Switchhouse
-
Free Standing Battery Charger
-
Mine Power Substation
-
On board Battery Charger
-
Protecting Cable