- The input may be through a coupler or a gland.
- The outside surfaces shall be essentially of fireproof construction.
- A maintained contact, push-to-operate, emergency-stop switch (to remove incoming power) shall be located in a conspicuous place on the enclosure. If the input cable is protected by a ground-wire monitor, the enclosure shall include a ground-wire monitor test switch. One switch may satisfy both requirements.
- The primary circuit shall include short-circuit and overload protection.
- A power transformer shall isolate the battery being charged from the incoming power source. Power transformers with concentrically wound primary and secondary windings shall include a Faraday shield.
- The secondary circuit shall include short-circuit and overload protection.
- The power transformer secondary and all battery charging circuits shall be electrically isolated from the frame ground of the charger.
- Each charger output shall be through a multi-conductor cable that includes separate grounding and interlock conductors.
- The electrical contacts of battery charging connectors shall be arranged to open the interlock circuit before the charging circuit.
- The interlock circuit shall remove power from the charger output using either a contactor or a circuit breaker with contacts opening all ungrounded conductors in either the primary or secondary circuit. The interlock circuit shall have a manual reset feature.
- A voltmeter, ammeter, or other device that indicates the battery state of charge shall be part of each charging circuit.
- The charger shall include an end-of-charge circuit. The circuit shall either stop the charging current or reduce it to a level that can be continued without causing excessive gassing or temperature. This level is normally 3 to 6 amperes per 100 ampere-hours of the battery's six-hour rating. A timer is an acceptable means of providing this protection.
-
Load Center
-
Surface Mine Fans
-
Track Mounted Carrier
-
Welding Cables
-
Stipulation of Settlement Between the PCA and DER DEP
-
Equipment Task Force
-
Miscellaneous Electrical Devices
-
Belt Starter
-
Branch Circuits and Taps
-
Circuit Breaker Switchhouse
-
Mine Power Substation
-
On board Battery Charger
-
Protecting Cable
-
Equipment Approvals